3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH). Operator has installed a new pump (Century Centurion Serial: 01219CH, 2.6 HP) to the system. Original pump was a Pentair WFE-8 with 2.0 HP.
Complete attached ERN form and send to ODH. Contact ODH to obtain approval for any construction/alterations before operating pool.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair. Observed loose handrail at steps leading into shallow end of pool.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. At time of inspection, a pH of approximately 8.0 was measured at the pool.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 26-August-2020
Comments |
---|
Observed gap in perimeter gutter system at entrance of pool. Documentation (make/model/year) on main drain cover is needed. Since last inspection, operator has installed a new pump to the system. See updated equipment inventory form for specifications. |