[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. -Observed the ORP was reading 575-600 during the inspection, but the flow switch was clogged, and the unit did not appear to be working properly. The free chlorine was 2.4 and the pH was 7.4, so the ORP reading should have been in the 750 range. CLEAN THE FLOW METER. TEST THE CHLORINE AND PH EVERY 4 HOURS UNTIL THE ACC IS FUNCTIONING PROPERLY.
Correct By: 26-Jun-2023
3701-31-04 (B)(1)(k) / Chemical storage or use shall not result in imminent health hazard.
Critical Chemical were being stored in a manner that could result in imminent health hazard.
Observed an old trichlor plastic container being used to store muriatic acid. The muriatic acid in the plastic container was being fed to the acid pump. IMMEDIATELY DISCONTINUE REUSING CHEMICAL CONTAINERS. DO NOT STORE MURIATIC ACID IN CONTAINERS OF OTHER CHEMICALS. Correct By: 22-Jun-2023
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly. -Observed the flow switch was clogged with debris, and it is not being tested monthly. CLEAN THE FLOW SWITCH AND TEST THE SWITCH MONTHLY TO ENSURE THE ACC IS OPERATING CORRECTLY.
Provide records indicating that the unit is being tested monthly. Correct By: 22-Jun-2023

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily. -Observed the water temperatures are not being recorded daily.
Take and record the water temperature at least once/day. Correct By: 22-Jun-2023
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly. -Observed the cyanuric acid is not being tested and recorded weekly.
Test for cyanuric acid level at least once/week. Correct By: 22-Jun-2023
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present -Observed there was no backflow prevention device available for inspection for the hose bibb that fills the pool. -OBTAIN A BACKFLOW PREVENTION DEVICE FOR THE HOSE BIBB.
Correct By: 26-Jun-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Corrected During Inspection Required turnover rates were not met. -Observed the flow rate was 55, which was below the required minium rate of 67 to achieve the proper turnover rate. -PIC backwashed the filters during the inspection, and the flow rate was increased to 90 gpm.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 20-June-2023


Comments
Our records indicate there were two Aquastar Wav9WR101 drain covers installed in June 2023. They have a five year life span and expire in June 2028.

The pH and free chlorine are to be tested every 4 hours while the pool is open when the ACC is not functioning properly.