3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not compliant covers for the skimmer equalizer outlets..
Install compliant outlet covers prior to placing the pool back into operation. PLACE VGB COVERS OVER THE SKIMMER EQUALIZER OUTLETS OR PLUG THE OUTLETS AT THE WALL.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Two skimmer weirs stick inside the skimmer.
All equipment must be maintained in accordance with the manufacturers specifications. MODIFY THE SKIMMER WEIRS SO THAT THEY FLOAT FREELY IN THE SKIMMER.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 05-July-2023


Comments
Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department.

Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room