3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Weirs are missing in the skimmers.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE WEIRS IN THE SKIMMERS. Correct By: 09-Aug-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
FLOW RATE MUST BE AT LEAST 71 GPM BUT LEAST THAN 74 GPM. CHECK THE FLOW METER, IT MAY BE STUCK Correct By: 16-Jul-2019
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not properly located.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
RELOCATE THE FLOW METER PER MANUFACTURER'S SPECIFICATIONS WHICH IS 10 TIME THE DIAMETER OF THE PIPE DOWN STREAM FROM TURBULENCE AND 5 TIME UP STREAM Correct By: 09-Jun-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
INCREASE pH TO 7.2 TO 7.8 Correct By: 11-Jul-2019
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
PLACE THE SHEPHERD'S CROOK ON A 12 FT POLE THAT IS NON-AJUSTABLE
PROVIDE A 30 FT ROPE FOR THE RING BUOY.
KEEP ALL SAFETY EQUIPMENT OUT AVAILABLE FOR USE WHEN THE POOL IS OPEN. Correct By: 16-Jul-2019
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not connected to a power source..
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
CONNECT THE EMERGENCY PHONE TO A POWER SOURCE. Correct By: 16-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-July-2019
Comments |
---|
Our records show: The main drain suction outlet cover (Paramount SDX 159-2212) was installed 7/1/2018. The cover has a 5 year life span and must be replaced before 7/1/2023. -The safety line between the deep and shallow end must be attached to the wall of the pool and not the deck. -check the fence at the bottom for opening and for lose fencing that can be lifted up -if the first aid kit is kept in the office post a sign stating its location. |