3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The equalizer lines are not VGB compliance. Covers are not on the outlet and the lines are not plugged.
PLUG THE EQUALIZER OUTLET AT THE POOL WALL OR INSTALL COMPLIANCE COVERS. Correct By: 12-Jul-2017
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Certificate of Compliance and the installation date were not available for the drain covers. The drain covers appear to be AquaStar WAV12 WR which have a life span of 5 years.
OBTAIN THE CERTIFICATE OF COMPLIANCE AND THE INSTALLATION DATE. IF THE DATE OF INSTALLATION IS NOT KNOWN THE DRAIN COVERS MUST BE REPLACED AT THE END OF THE SEASON (BEFORE THE START OF THE NEXT SEASON). KEEP THE CERTIFICATE OF INSTALLATION, THE INSTALLATION INSTRUCTIONS, AND THE CERTIFICATE OF INSTALLATION. Correct By: 05-May-2018
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The acid container is not labeled.
LABEL THE ACID CONTAINER. Correct By: 12-Jul-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The skimmer weirs are missing in the skimmers.
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL WEIRS IN THE SKIMMERS TO IMPROVE SKIMMING. Correct By: 12-Jul-2017
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. The hose bib by the pool does not have a backflow preventer.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB BY THE POOL. Correct By: 12-Jul-2017
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Repeat Corrected During Inspection Throttle valve was not properly maintained/labeled.
LABEL THE THROTTLE VALVE WITH THE MAX ALLOWABLE FLOW (240 GPM) AND THE MINIMUM REQUIRED FLOW (67 GPM). Correct By: 12-Jul-2017
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. The flow meter is not working and the flow meter is not properly located. The flow meter is a Blue White F-300 which requires 5 time the diameter of the pipe downstream from the elbow and 2 times the diameter of the pipe upstream from the elbow.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. RELOCATE THE FLOW METER (BLUEWHITE f-300) 15 INCHES DOWNSTREAM FROM THE NEAREST TURBULENCE AND 6 INCHES FORM THE NEAREST TURBULENCE UPSTREAM. Correct By: 12-Jul-2017
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use. POST REQUIRED SIGN. Correct By: 12-Jul-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-July-2017