[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH). The circulation pump Hayward SP2610X15 was replaced with a Hayward SV700.
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO ODH FOR THE REPLACEMENT OF THE CIRCULATION PUMP. Correct By: 07-Jun-2023
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL A VACUUM BREAKER ON THE HOSE BIB IN THE EQUIPMENT ROOM. Correct By: 07-Jun-2023
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces had standing water or other hazards. Concrete is uneven.
Repair areas of the deck where the concrete is uneven. REPAIR THE DECK TO ELIMINATE TRIPPING AND TOE INJURY HAZARDS.. Correct By: 07-Jun-2023
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Repeat Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. LOWER THE CYA LEVEL TO 70 PPM OR LESS. Correct By: 07-Jun-2023
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. THE EMERGENCY PHONE MUST BE LOCATED SO AS TO BE ACCESSIBLE AT ALL TIMES. IT CAN NOT BE LOCATED INSIDE THE EQUIPMENT ROOM. Correct By: 31-May-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 31-May-2023


Comments
Ensure the flow rate is between 58 and 122 gpm. You might want to adjust it up a bit.

The Certificate of Compliance is not available for the main drain cover. One was supplied to operator with the inspection report. Keep a copy at the facility for future review. Our records show that the main drain suction outlet covers (Lawson MLD-FGD-0909) were installed 5/1/2017. The covers have a 10 year life span and must be replaced before 5/1/2027.

Keep a pump onsite to drain the pool.

Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.