3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEATH HAZARD. THE OPERATOR CLOSED THE WADING POOL AND IT CONTINUES TO BE CLOSED. Correct By: 08-Jun-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
THE FLOW METER IS STUCK. REPAIR OR REPLACE.
Facility Type: Special Use
[?] Inspection Type: Follow-up
Inspection Date: 10-June-2022
Comments |
---|
THE WADING POOL REMAINS CLOSED. A REINSPECTION WILL BE MADE AT A LATER DATE TO VERIFY COMPLIANCE. |