3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Corrected During Inspection ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
RECORD WATER TEMPERATURE DAILY AND ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 30-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-June-2023
Comments |
---|
Chemical feeder pumps should not be mounted above other chemical feeder pumps or chemical containers to prevent possible mixing of chemicals and producing toxic gas. If chlorine is mixed with muriatic acid chlorine gas is formed, which can lead to severe injuries and fatalities (SIFs) to exposed individuals. Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 5/19/2021. The covers have a 7 year life span and must be replaced before 5/19/2028. |