3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT ERN TO ODH FOR THE PUMP REPLACEMENT.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Weirs missing in skimmers.
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL WEIRS IN SKIMMERS.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-July-2023
Comments |
---|