[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT ERN TO ODH FOR THE PUMP REPLACEMENT.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Weirs missing in skimmers.
All equipment must be maintained in accordance with the manufacturers specifications. INSTALL WEIRS IN SKIMMERS.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 27-July-2023


Comments
FLOW RATE SHOULD BE INCREASED TO 175 GPM.

Equipment requiring ODH plan approval has been replaced since the inventory report dated 6-29-21 without submitting an ERN to ODH. The circulation pump Pentair Challenger CFII-N1-5FE 5 Hp was replaced with a Pentair WhisperFlo 5 Hp.