3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE FUNCTION OF THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH MONTHLY ON THE LOG SHEET THAT IS KEPT AT THE POOL. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
PROVIDE THE PUMP CURVE AND CALCULATIONS FOR DETERMINING THE FLOW RATE FOR THE SPA JET PUMP. Correct By: 30-Jun-2018
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 20-June-2018