3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH. Correct By: 30-Jul-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-July-2021
Comments |
---|
All corrections made since the last inspection dated 6-30-21 -new main drain covers were installed -CYA level is acceptable (under 70 ppm) -ORP level acceptable (over 650) IT APPEARS THAT YOU HAVE 2 DIFFERENT VERSIONS OF THE WEEKLY LOG SHEET. BE CAREFUL NOT TO MIX UP THE CALCIUM HARDNESS ND THE CYANURIC ACID OR THE TOTAL AND COMBINE CHLORINE ON THE SHEET. EITHER SHEET IS ACCEPTABLE. |