3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly. The flow switch/pump interlock was not tested and recorded monthly.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH/PUMP INTERLOCK FUNCTION MONTHLY. Correct By: 16-Jun-2017
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not properly maintained/adjusted. The throttle valve was not tagged.
TAG THE THROTTLE VALVE WITH THE MAX ALLOWABLE FLOW AND THE MIN REQUIRED FLOW OR PLACE ON THE PIPE BY THE FLOW METER. MAX FLOW IS 566 GPM AND THE MIN IS 314 GPM. Correct By: 16-Jun-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. Depth markings were more than 25 ft apart.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
DEPTH MARKINGS AND "NO DIVING" MARKINGS MUST BE NO MORE THAN 25 FT APART. ADD DEPTH AND "NO DIVING" MARKINGS WHERE THEY ARE MORE THAN 25 FT APART Correct By: 10-Jul-2017
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
PROVIDE A RING BUOY WITH A 30-60 FT ROPE. Correct By: 16-Jun-2017
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
A sign identifying the location of the emergency phone was not posted.
POST A SIGN THAT CAN BE SEEN AT POOL SIDE THAT STATES THE LOCATION OF THE EMERGENCY PHONE. Correct By: 16-Jun-2017
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 09-June-2017
Comments |
---|
AN AIR GAP IS NOT PROVIDED FOR THE BACKWASH LINE FOR THE FILTERS. THE OUTLET IS SUBMERGED IN A DEEP PIT. |