3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not compliant covers. Main drain covers have expired.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation.
REPLACE THE MAIN DRAIN COVERS RIGHT AWAY. Correct By: 02-Jul-2021
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 02-Jul-2021
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
LOWER CYANURIC ACID. Correct By: 02-Jul-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-June-2021
Comments |
---|
When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed on 10-1-12. The covers have a 7 year life span and must be replaced before 10-1-19. |