3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC MONTHLY. Correct By: 26-Jun-2019
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The disinfection chemical feeder was changed without approval. The pump was changed without approval.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE DISINFECTION CHEMICAL FEEDER. PLEASE CHECK WITH ODH TO DETERMINE IF THEY REQUIRE REVIEW OF THE CIRCULATION PUMP REPLACEMENT. Correct By: 01-Jul-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The weir in the skimmer is missing.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE WEIR IN THE SKIMMER Correct By: 10-Jul-2019
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A PRESSURE AND VACUUM GAUGE ON THE SPA JET PUMP FOR DETERMINING THE FLOW RATE. POST THE PUMP CURVE AND THE CALCULATION FOR DETERMINING THE GPM FLOW RATE. Correct By: 24-Jul-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
INCREASE pH. Correct By: 26-Jun-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY. Correct By: 26-Jun-2019
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 24-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (AquaStar WAV 12) was installed 5/26/2018. The cover has a 5 year life span and must be replaced before 5/26/2023. -5.1(F)(2) Flow measuring devices. A means of determining rate-of-flow shall be properly installed and maintained on all public swimming pools, special features and jet pumps so that the rate of flow can be accurately determined and easily observed. One of the following methods to measure flow shall be used: (a) A flow meter; or (b) A pump curve specific for the pump and impellor. The pump curve shall be conspicuously posted in the filter room and shall be marked up to display the formula or means for calculating the gauge readings into the total dynamic head (TDH) and the flow in gallons per minute (gpm). A functional compound gauge shall be installed on the suction side of the pump, at or near the hair and lint strainer. A functional pressure gauge shall be installed on the pressure side of a pump, at or near the impellor housing; - |