[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. ERN HAS BEEN SUBMITTED TO ODH PER OPERATOR. WAITING FOR ODH APPROVAL.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO 69 GPM OR MORE BUT LESS THAN 120 GPM.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times. PLACE FIRST AI KIT IN THE POOL AREA.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. REPAIR EMERGENCY PHONE. Correct By: 18-Jul-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 11-July-2023


Comments
MAIN DRAIN COVERS EXPIRE ON 7-27-23. REPLACE COVERS BEFORE THEN AND RETAIN CERTIFICATE OF COMPLIANCE.