3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat The pump room was not locked.
KEEP PUMP ROOM LOCKED
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Weirs are missing in the skimmers
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL WEIRS IN THE SKIMMERS.
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
CUT DISCHARGE PIPE SHORTER TO PROVIDE AN AIR GAP ON THE FILTER BACKWASH LINE
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE CIRCULATION FLOW TO BETWEEN 244 AND 423 GPM Correct By: 24-Jul-2019
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
3701-31-04 (E)(2)(b)(ii) / A back/spine board with straps and head immobilizers
Repeat A back/spine board with straps and head immobilizers was not provided at the guarded pool.
Provide a back/spine board with straps and a head immobilizer at the pool at all times.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 22-July-2019