[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Our records show that the drain covers have expired.
REPLACE THE DRAIN COVERS OR PROVIDE DOCUMENTATION OF THE DATE OF INSTALLATION AND THE CERTIFICATE OF COMPLIANACE. Correct By: 10-Jun-2019
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer outlets are not covered with a vgb compliant cover.
PLUG THE SKIMMER EQUALIZER OUTLET AT THE POOL WALL OR COVER THE OUTLET WITH A VGB COMPLIANT COVER. Correct By: 10-Jun-2019

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. PLACE THE 2 WEIRS IN THE SKIMMERS REQUIRING WEIRS. Correct By: 12-Jun-2019
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely. PROVIDE AN AIR GAP ON THE FILTER BACKWASH DISCHARGE LINE. Correct By: 12-Jun-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE THE FLOW RATE TO AT LEAST 122 GPM. Correct By: 12-Jun-2019
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency number not posted at the emergency phone.
Ensure that the emergency device is functioning properly and emergency numbers at posted. POST "DIAL 911 IN CASE OF EMERGENCY" BY THE EMERGENCY PHONE. Correct By: 12-Jun-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 10-June-2019


Comments
our records show: The main drain suction outlet cover (New Water Solutions DS 360) was installed on an unknown date. The cover has a 5 year life span and must be replaced before 5/1/2019.