3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The Certificate of Compliance and installation instructions were not available for the main drain covers.
OBTAIN THE CERTIFICATE OF COMPLIANCE AND INSTALLATION INSTRUCTIONS FOR THE MAIN DRAIN COVERS. POST THE COC IN THE EQUIPMENT ROOM. OUR RECORDS SHOW THAT THE COVERS WERE REPLACED 5/23/2017 AND MUST BE REPLACED 5/23/2024.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored in unsafe manner.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
STORE ALL CHEMICALS OFF OF THE FLOOR. STORE LIQUID CHEMICALS ON LOWER SHELVES THAN DRY CHEMICALS.
3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
The ventilation in the equipment room has been blocked.
3701-31-05.1(R) required the ventilation in the equipment room to be in accordance with Chapter 3781 and 3791 of the ORC and meet building codes.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records twice a day. ACC flow switch not tested and recorded
All facility records must be maintained and available for review upon request.
RECORD CHLORINE AND pH TWICE DAILY. RECORD AUTOMATIC CHEMICAL CONTROLLER FUNCTION MONTHLY.
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Replacement pipe was not rigid PVC or equivalent. A rubber coupling was on a pipe.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools.
REPLACE THE RUBBER COUPLING WITH RIGID PIPE.
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention devices were not maintained to function properly
Have the backflow prevention device replaced so that backflow is prevented.
REINSTALL BACKFLOW PREVENTER ON THE HOSE BIB IN EQUIPMENT ROOM
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces was dirty.
CLEAN THE DECK.
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
A thermometer for testing the temperature of the water was not available.
PROVIDE A THERMOMETER FOR THE CHECKING WATER TEMPERATURE.
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
PROVIDE A ROPE ON THE RIPE BUOY THAT IS 30-60 FEET LONG AND 1/4 INCH THICK.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-April-2019
Comments |
---|
The lighting was not checking. Let will be checked at the time of the next inspection. A tile deck was installed over the spa area. The tile appears to be slippery. I will search further guidance on the acceptability of the tile. I will check on the necessity of ventilation n the equipment room. |