[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT AN ERN TO ODH FOR THE PUMP REPLACEMENT.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. THE SVRS DOES NOT APPEAR TO BE FUNCTIONING PROPERLY. CHECK THE SVRS AND RECORD RESULTS ON THE WEEKLY LOG SHEETS. Correct By: 13-Apr-2023


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 12-April-2023


Comments
The ORP sensor may need to be cleaned, calibrated, or changed. The ORP reading was 605 mv, but the free chlorine reading was 10.8 ppm.

The circulation pump Sta-Rite PE5D-181L .75 HP was replaced with a Pentair Intelliflo VSF

CDC DOES NOT RECOMMEND CHLORINE LEVELS HIGHER THAN 10 PPM