3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical The ACC unit was not activating an audible or visual alarm when unit malfunctioned or when pH or ORP levels were not acceptable.
-Have the ACC unit serviced or replaced so that the audible or visual alarm is activated when necessary.
Correct By: 18-Mar-2024
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
-Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm.
- Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Correct By: 15-Mar-2024
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
-Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-March-2024
Comments |
---|
- Contact Lorain County Public Health for re-inspection before reopening the pool. - Chlorine level must be brought up to above 1ppm. - Flow switch must be tested monthly and documented once the ACC has been recalibrated/ fixed. - Missing screw on drain cover. - Algal growth on drain covers. - ERN must be filled out and sent to Ohio Department of Health for pump replacement. |
-The Certificate of Compliance for the main drain covers is available in the equipment room. |