3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas.
KEEP THE EQUIPMENT ROOM LOCKED. Correct By: 03-Jul-2021
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
TEST AND RECORD CYANURIC ACID WEEKLY. Correct By: 03-Jul-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The weirs in the skimmers do not float freely.
All equipment must be maintained in accordance with the manufacturers specifications.
MODIFY THE WEIRS IN THE SKIMMERS SO THAT THEY FLOAT FREELY WITH THE WATER. Correct By: 03-Jul-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 03-Jul-2021
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit provided was not in good repair. Expired reagents.
Maintain the test kit in good repair to conduct water quality tests.
REPLACE EXPIRED REAGENTS. Correct By: 03-Jul-2021
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was in poor condition.
Provide a proper floatation device at all times.
REPLACE THE ROPE ON THE RING BUOY. Correct By: 03-Jul-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-July-2021
Comments |
---|
KEEP THE RING BUOY VISIBLE AND AVAILABLE FROM THE POOL AREA. KEEP A COPY OF THE MAIN DRAIN CERTIFICATE OF COMPLIANCE AT THE FACILITY Our records show that the main drain suction outlet covers (AquaStar WAV12) were installed 6/1/2019. The covers have a 5 year life span and must be replaced before 6/1/2024. |