3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain covers were not installed according to the manufacturer instructions.
INSTALL THE MAIN DRAIN COVERS ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS. USE THE PROPER FRAME AND SCREWS. Correct By: 09-Jun-2019
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer outlets are not covered with a VGB cover.
PLUG THE EQUALIZER LINES AT THE POOL WALL, OR COVER THE OUTLET WITH A VGB COMPLIANT COVER Correct By: 09-Jun-2019
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The filter and chlorinator was replaced with approval from ODH.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE FILTER AND THE CHLORINATOR. Correct By: 09-Jun-2019
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST AND RECORD FREE, COMBINE, AND TOTAL CHLORINE EVERY FOUR HOURS, WATER TEMPERATURE DAILY, AND CYANURIC ACID WEEKLY. Correct By: 09-Jun-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIRS IN THE SKIMMERS. Correct By: 09-Jun-2019
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
INSTALL AN AIR GAP ON THE DRAIN FROM THE FILTER BACKWASH. Correct By: 09-Jun-2019
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces had standing water or other hazards.
Repair areas of the deck where standing water is occurring.
REPAIR THE DECK WHERE THE TILE HAS BEEN REMOVED. Correct By: 09-Jun-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY. Correct By: 09-Jun-2019
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
Provide a proper floatation device at all times.
ATTACH A 30-60 FT ROPE ON THE RING BUOY. Correct By: 09-Jun-2019
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
KEEP A FIRST AID KIT IN THE POOL AREA Correct By: 09-Jun-2019
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
REPAIR THE EMERGENCY PHONE. Correct By: 09-Jun-2019
3701-31-04 (E)(3)(d) / "WARNING or DANGER - POOL CLOSED" sign(s) posted-when the pool is closed
The pool was closed but the "WARNING or DANGER - POOL CLOSED" sign(s) were not posted.
Post the "WARNING or DANGER - POOL CLOSED" sign at all times the pool is not available for use. Correct By: 09-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 06-June-2019