3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. WADING POOL WAS CLOSED AT THE TIME OF INSPECTION. CALL ME WHEN THE VIOLATION IS CORRECTED. 440-219-7158. Correct By: 15-Jun-2021
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
CONTACT THE OHIO DEPARTMENT OF HEALTH FOR APPROVAL OF THE FENCE. Correct By: 15-Jun-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 56 GPM. Correct By: 15-Jun-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 15-Jun-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY. Correct By: 15-Jun-2021
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 15-June-2021
Comments |
---|
THE CHLORINE TANK APPEARS TO BE EMPTY. |