[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool. SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FOR THE REPLACEMENT OF THE PUMP. Correct By: 09-Jun-2022
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present
Remove all cross connection hazards from the pool area. PROVIDE AN AIR GAP ON THE FILL LINE TO THE POOL. Correct By: 04-Jun-2022
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
REPEAT Backflow prevention devices were not maintained to function properly
Have the backflow prevention device installed. INSTALLASSE 1011 BACKFLOW PREVENTERS ON THE HOSE BIBS IN THE EQUIPMENT ROOM. Correct By: 09-Jun-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST pH. Correct By: 04-Jun-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 03-June-2022


Comments
Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.

The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 10/3/2018. The covers have a 7 year life span and must be replaced before 10/3/2025. WRITE THE CORRECT DATE ON THE CERTIFICATE.

The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions.