3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc) clearly.
Do not operate the pool when water clarity is poor.
TREAT POOL IF NECESSARY. DO NOT OPEN POOL UNTIL BOTTOM CAN BE CLEARLY SEEN. Correct By: 27-Apr-2022
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were not used properly..
USE ONLY THE CHEMICAL SPECIFIED BY THE MANUFACTURER OF THE CHLORINATOR. DO NOT USE THE CCH CHLORINE TABLETS. ONLY USE THE BLUE AQUA TABS. Correct By: 28-Apr-2022
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
DO NOT STORE CHLORINE TABLETS ON TOP OF THE ALKALINITY UP (SODIUM BICARD). Correct By: 27-Apr-2022
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Replacement pipe was not rigid PVC or equivalent.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools.
REMOVE BLACK ELECTRICAL TAPE FROM THE PIPE AND REPAIR LEAK IF ONE EXISTS. Correct By: 04-May-2022
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable.
REPAIR THE DOOR SO THAT IT SELF-CLOSES AND LATCHES. Correct By: 27-Apr-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 28-Apr-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 26-April-2022
Comments |
---|
The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Hayward WG1048) were installed 3/4/2017. The covers have a 7 year life span and must be replaced before 3/4/2024. Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. |