3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. THE FLOW SWITCH WAS UNPLUGGED FROM THE ACC.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR ACC FLOW SWITCH. Correct By: 21-Jun-2023
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FLOW SWITCH MONTHLY AND AND BEFORE OPENING FOR THE YEAR. Correct By: 20-Jun-2023
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE CHLORINE PUMP.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 31 GPM. Correct By: 27-Jun-2023
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches. 8 inch gap under the fence.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
MODIFY THE FENCE TO ELIMINATE THE GAP UNDER THE FENCE.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 22-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-June-2023
Comments |
---|
The Certificate of Compliance is not available for the main drain cover. Keep a copy at the facility for future review. |