3701-31-04(D)(6)(a)(4) / Spa free chlorine disinfectant residual shall be above 2 ppm.
Critical Spa free chlorine disinfectant residual was below 2 ppm.
-Observed the free chlorine in the spa to be 0.2 ppm
DO NOT OPERATE THE SPA UNTIL THE CHLORINE IS 2ppm OR ABOVE.
3701-31-04 (B)(2) / Authorized representative is on-site or within 30 minutes of pool location
Authorized representative was not on-site or within 30 minutes of pool location.
-After observing the free chlorine was less than 2 ppm, the operator was contacted, and they did not respond within the required 30 minutes.
MAKE ARRANGEMENTS TO HAVE AN AUTHORIZED REPRESENTATIVE AVAILABLE WHILE THE POOL IS IN OPERATION.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
-Observed the pH to be 8.0.
TREAT THE SPA SO THE pH IS BETWEEN 7.2-7.8.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
-Observed the total alkalinity to be 50ppm
RAISE THE TOTAL ALKALINITY TO BE AT LEAST 60 ppm.
3701-31-04 (C)(8) / Spa water is drained at least every 30 days and is recorded
Spa water was not recorded as being drained in the last 30 days.
-Observed the spa has not been recorded as being drained within the past 30 days.
DRAIN THE SPA IMMEDIATELY AND CLEAN BEFORE PLACING THE SPA BACK INTO OPERATION.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 04-August-2023
Comments |
---|
-Observed in the records that the chlorine level has been recorded as being less than 2ppm on some days. There were no notes about adjusting the chlorine or retesting the chlorine to ensure it was above 2ppm on those days. THE SPA IS TO BE CLOSED IF THE CHLORINE IS LESS THAN 2.0ppm, AND IT IS NOT TO BE REOPENED UNTIL IT IS RETESTED AND ACHIEVES 2.0ppm OR GREATER. If the certificates of compliance with installation dates for the drain covers are not provided, new main drain covers will be required. |