[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Disinfection system was not operating properly at the time of the inspection
Do not operate the pool when disinfection system is not operating properly. Ensure that the disinfection system is functioning properly prior to placing the pool back into operation. IF THE DISINFECTION FEEDER CANNOT BE INSTALLED WITHIN 2 DAYS CLOSE THE POOL UNTIL NEW FEEDER IS INSTALLED. HAND FEEDING CAN NOT BE CONTINUOUS DONE. Correct By: 08-Jun-2022

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. ADJUST THE WEIR IN THE SKIMMER SO THAT IT FLOWS FREELY WITH THE WATER LEVEL. Correct By: 13-Jun-2022
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL AN ASSE 1011 VACUUM BREAKER ON THE HOSE BIB IN THE EQUIPMENT SHED. Correct By: 13-Jun-2022
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable. REPAIR THE FENCE SO THAT IT SELF-CLOSES AND LATCHES. Correct By: 13-Jun-2022
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. REDUCE THE CYANURIC ACID TO BELOW 70 PPM. Correct By: 13-Jun-2022
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment without gloves.
Provide first aid equipment, including a first aid kit, at the pool at all times. PROVIDE GLOVES FOR THE FIRST AID KIT. Correct By: 13-Jun-2022
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. REPAIR THE EMERGENCY PHONE. Correct By: 13-Jun-2022
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use. POST REQUIRED SIGNS Correct By: 13-Jun-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-June-2022