[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow rate through the filters is higher than allowable. The flow is 42 gpm and the maximum allowable flow is 38 gpm.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO BETWEEN 32 AND 38 GPM. Correct By: 17-Jun-2017
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not properly maintained/adjusted. The throttle valve is not tagged.
TAG THE THROTTLE VALVE WITH THE MAXIMUM ALLOWABLE FLOW AND THE MINIMUM REQUIRED FLOW OR PLACE THE MAX AND MIN ON THE PIPE BY THE FLOW METER. MAX 38 GPM, MIN 32 GPM. Correct By: 17-Jun-2017


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 09-June-2017


Comments
The flow meter was changed since last year. Record of change was recorded incorrectly on the inventory report, but changes could not be made to the report since the report was locked after printing.

The new flow meter was located incorrectly. The flow meter is 18 inches from the turn in the pipe downstream. The pipe is 2 inches in diameter.

Other violations for the entire facility are recorded on the Main Pool inspection report.

THE AUTOMATIC CHEMICAL CONTROLLER IS NOT LISTED ON THE ODH APPROVED LIST.