[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. RECORD ALKALINITY READINGS WEEKLY. Correct By: 06-Apr-2022
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
The test results for these devices must be kept on site for review. TEST AND RECORD FLOW SWITCH RESULTS AT LEAST MONTHLY. Correct By: 06-Apr-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH. 7.5 IS IDEAL. Correct By: 06-Apr-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 05-April-2022


Comments
Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.

The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (AVSCO A+A Manu AAMFG 832) were installed 5/23/2017. The covers have a 7 year life span and must be replaced before 5/23/2024.

The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions.