[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is .2 which is less than required.
This violation is a critical operational item and poses an imminent health hazard. INCREASE THE FREE CHLORINE LEVEL TO AT LEAST 1 PPM. THE POOL MUST CLOSE UNTIL THE VIOLATION IS CORRECTED. CALL THE HEALTH DEPARTMENT WHEN THE VIOLATION IS CORRECTED. Correct By: 20-Jun-2018
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. THE POOL MUST CLOSE UNTIL THE ACC IS OPERATING PROPERLY. Correct By: 20-Jun-2018

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE THE FLOW RATE TO AT LEAST 68 GPM BUT LESS THAN 98 GPM Correct By: 30-Jun-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 23-Jun-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 23-Jun-2018
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times. Correct By: 30-Jun-2018
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use. Correct By: 30-Jun-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 20-June-2018