[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The main drain covers have exceeded their life span.
REPLACE THE MAIN DRAIN COVERS. RETAIN THE CERT OF COMPL, INSTALL INSTRUCTIONS, AND CERT OF INSTALL Correct By: 15-May-2019

3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely. INSTALL AN AIR GAP ON THE FILTER BACKWASH DISCHARGE LINE. Correct By: 28-Jul-2018
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR OR REPLACE THE FLOW METER. KEEP FLOW BETWEEN 14 AND 26 GPM. Correct By: 28-Jul-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 21-July-2018