3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THE FREE CHLORINE LEVEL WAS .4 UPON FIRST CHECKING. THE OPERATOR IMMEDIATELY ADJUSTED THE ACC AND THE LEVEL ROSE TO 3 PPM WITHIN 30 MINUTES.
MORE FREQUENT CHECKING OF THE FREE CHLORINE LEVEL IS ADVISED. Correct By: 30-Jun-2022
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE DISINFECTION CHEMICAL FEEDER PUMP BLUE WHITE FLEXFLO A1N20A-4T WITH A A1N20A-7T. Correct By: 07-Jul-2022
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST THE ALKALINITY. Correct By: 02-Jul-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-June-2022