3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas.
KEEP EQUIPMENT ROOM LOCKED. Correct By: 24-Mar-2021
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST AND RECORD ON THE LOG SHEETS THE ACC FUNCTION. Correct By: 24-Mar-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
IF THE FLOW RATE CANNOT BE INCREASED TO AT LEAST 54 GPM, A NEW PUMP MAY NEED TO BE INSTALLED.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 23-March-2021
Comments |
---|
Our record show that the main drain suction outlet cover (New Water Solutions DS 360) was installed on 10/26/2018 . The cover has a 5 life span and must be replaced before 10/26/2023. Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. |