3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib in the pump room is not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A ASSE 1011 BACKFLOW PROVENTER ON THE HOSE BIB IN THE PUMP ROOM. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate does not self-close and latch.
REPAIR THE GATE SO THAT IT SELF-CLOSES AND LATCHES. (EAST SIDE GATE) Correct By: 09-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 02-July-2019
Comments |
---|
Our records show: The main drain suction outlet cover (Lawson MLD SG 1212) was installed 9-3-18. The cover has a 10 year life span and must be replaced before 9-3-28. -THERE IS A CONCERN ABOUT THE LOCATION OF THE EMERGENCY PHONE. IT IS LOCATED IN THE PUMP ROOM WHERE CHEMICALS AND EQUIPMENT ARE STORE. THIS APPEARS TO BE IN CONFLICT WITH THE REQUIREMENT THAT EQUIPMENT AND CHEMICAL STORAGE AREAS BE ACCESSIBLE ONLY TO AUTHORIZED PERSONAL. THE EMERGENCY PHONE MAY NEED TO BE MOVED OUTSIDE OF THE PUMP ROOM AND THE PUMP ROOM LOCKED. I WILL CONSULT WITH THE OHIO DEPARTMENT OF HEALTH AS TO WHY THEY APPROVED THIS LOCATION. I WILL NOTIFY YOU WHEN A DEFINITE DETERMINATION IS MADE. -Have the backflow preventer inspected annually and maintain documentation of inspection at the facility. |