3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The skimmer equalizer outlets are not covered with an approved cover.
INSTALL VGB APPROVED COVERS OVER THE SKIMMER EQUALIZER OUTLETS OR PLUG THE OUTLET AT THE POOL WALL. Correct By: 15-Jul-2019
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
ENSURE THAT TESTING IS COMPLETED: FREE CHLORINE, COMBINE CHLORINE, AND TOTAL CHLORINE, AND pH EVERY 12 HOURS, WATER TEMPERATURE DAILY, ALKALINITY WEEKLY, AND ACC FUNCTION MONTHLY. Correct By: 02-Jul-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Weirs were missing in the skimmers.
All equipment must be maintained in accordance with the manufacturers specifications.
PLACE THE WEIRS IN THE SKIMMER ONCE THEY ARE OBTAINED. Correct By: 15-Jul-2019
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
KEEP REACH POLE WITH SHEPHERD'S CROOK ON POOL DECK AREA ONCE IT IS OBTAINED. Correct By: 15-Jul-2019
3701-31-04 (E)(2)(b)(ii) / A back/spine board with straps and head immobilizers
A back/spine board with straps and head immobilizers was not provided at the guarded pool.
Provide a back/spine board with straps and a head immobilizer at the pool at all times.
KEEP THE SPINE BOARD OUT ON THE POOL DECK AREA WHILE OPEN. Correct By: 02-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-July-2019
Comments |
---|
Our records have been updated to show: The main drain suction outlet cover (Waterway 640-472xV) was installed on 6-1-19. The cover has a 7 year life span and must be replaced before 6-1-26 |