3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE LEAKING PIPE IN THE EQUIPMENT ROOM. Correct By: 31-Jul-2020
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
Obtain fresh reagents and store them properly.
STORE REAGENTS IN A DARK LOCATION. Correct By: 31-Jul-2020
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
REATTACH THE HOOK ON THE SHEPHERD'S CROOK. Correct By: 31-Jul-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 29-July-2020
Comments |
---|
The main drain suction outlet cover (Waterway 640-472xV) was installed on 5/22/2019. The cover has a 7 year life span and must be replaced before 5/22/2026. The cover has a flow rating of 356 gpm. CHECK TO MAKE SURE THAT ALL 4 SCREWS ARE IN PLACE ON THE DRAIN COVERS. |