[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Skimmer are missing the weirs.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE WEIRS IN THE SKIMMERS
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. The flow meter indicator is stuck at the bottom reading 0. The flow meter is not properly located
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR THE FLOW METER. RELOCATE THE FLOW METER 10 TIMES THE PIPE DIAMETER DOWNSTREAM FROM THE ELBOW OR OTHER TURBULENCE AND 5 TIMES THE PIPE DIAMETER UPSTREAM FROM THE ELBOW OR OTHER TURBULENCE


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 21-August-2019


Comments
When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm