[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. THIS VIOLATION IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE POOL UNTIL CORRECTED. OPERATOR CLOSED POOL AT END OF INSPECTION

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The type of chlorine specified for the chlorinator was not being used.
All equipment must be maintained in accordance with the manufacturers specifications. USE THE CHLORINATOR ACCORDING TO THE MANUFACTURER'S DIRECTIONS. DO NOT USE SODIUM CHLORIDE IN THE EROSION FEEDER.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL BACKFLOW PREVENTER (VACUUM BREAKER ASSE 1011) ON THE THREE HOSES. TWO ARE IN THE EQUIPMENT ROOM AND ONE IS OUTSIDE THE EQUIPMENT ROOM.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR OR REPLACE FLOW METER Correct By: 09-Aug-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable. REPAIR GATE
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times. KEEP FIRST AID KIT AVAILABLE FOR SWIMMERS. Correct By: 11-Aug-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 16-August-2021


Comments
OPERATOR INDICATED THAT THE POOL REMAINS CLOSED DUE TO THE LACK OF TRICHLOR TABLES AND WILL REMAIN CLOSED UNTIL HE RECEIVES IT AND LEVELS ARE ACCEPTABLE.