3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Each drain cover is missing a screw to secure it.
REPLACE THE MISSING SCREW IN THE DRAIN COVER. Correct By: 02-Jul-2020
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
MAINTAIN THE ORP Correct By: 02-Jul-2020
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY ON THE LOG SHEET. TEST AND RECORD THE EMOTRON (SVRS) FUNCTION MONTHLY AND RECORD IT ON THE LOG SHEET. Correct By: 02-Jul-2020
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. The flow meter for the jet pump is not functioning.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE JET PUMP FLOW METER. Correct By: 02-Jul-2020
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
ADJUST THE CYANURIC ACID Correct By: 27-Jun-2020
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 25-June-2020
Comments |
---|
When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. Our records show that the main drain suction outlet cover (AquaStar WAV12) was installed on 5/31/2019. The cover has a 5 yr lifespan and must be replaced before 5/31/2024. |