3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The ACC is not functioning properly. It is reading far less chorine level than the actual level.
REPAIR THE ACC SO THAT IT DISPLAYS CHEMICAL LEVELS ACCURATELY AND ADJUSTS CHEMICALS TO ACCEPTABLE LEVELS. Correct By: 23-Aug-2017
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Chemical readings were not accurate.
OPERATOR SHOULD BECOME MORE FAMILIAR WITH THE TEST KIT. Correct By: 23-Aug-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The automatic chemical controller is not operating properly. It continues to add/make chlorine even though the level is more than 20 ppm. The displace shows less than 1 ppm.
All equipment must be maintained in accordance with the manufacturers specifications.
HAVE THE AUTOMATIC CHEMICAL CONTROLLER REPAIRED OR REPLACED. Correct By: 20-Aug-2017
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 08-Jun-2017
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 08-Jun-2017
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The reach pole is 15 ft.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
SHORTEN THE REACH POLE TO 12 FT. Correct By: 20-Aug-2017
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 21-August-2017
Comments |
---|
SERVICE COMPANY WAS CALLED DURING THE INSPECTION. HE SHOULD ARRIVE WITHIN 2 HOURS. CHLORINE TESTING 1. FILL BIG TUBE TO 25 ml MARK WHICH IS ABOUT 1/2 FULL. 2. ADD 2 SCOOPS OF POWDER. SWIRL UNTIL MIXED. 3. ADD DROPS FROM #0870 BOTTLE. IT IS ONE OF THE BROWN BOTTLES. COUNT DROPS UNTIL THE WATER TURNS CLEAR. 4. MULTIPLE DROPS BY .2 TO GET FREE CHLORINE. EXAMPLE 7 DROPS EQUALS 1.4 ppm FREE CHLORINE. 7 X .2 = 1.4 5. ADD 5 DROPS OF #3 BOTTLE. SWIRL. 6. ADD DROPS FROM #0870 BOTTLE. COUNT DROPS UNTIL THE WATER TURNS CLEAR. 7. MULTIPLE DROPS BY .2 TO GET COMBINE CHLORINE. 8. ADD COMBINE AND FREE CHLORINE TO GET TOTAL CHLORINE. |