3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow switch was not tested monthly
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FLOW SWITCH FUNCTION EVERY 30 DAYS. Correct By: 21-Jul-2023
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
RECORD WATER TEMPERATURE DAILY. Correct By: 21-Jul-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 21-Jul-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-July-2023