[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required flow meter was not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR THE FLOW METER. Correct By: 20-Sep-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH AFTER REDUCING THE CHLORINE LEVEL. Correct By: 20-Sep-2023
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. ADJUST THE ALKALINITY AFTER REDUCING THE CHLORINE LEVEL. Correct By: 20-Sep-2023


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 18-September-2023


Comments
CDC DOES NOT RECOMMEND CHLORINE LEVELS HIGHER THAN 10 ppm.