[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Skimmer weirs were missing
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE WEIRS IN THE SKIMMERS. Correct By: 02-Jul-2021
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. TIGHTEN THE HAND RAIL ON THE STEPS. Correct By: 02-Jul-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable. REPAIR THE GATE SO THAT IT SELF-CLOSES AND SELF-LATCHES Correct By: 02-Jul-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH Correct By: 02-Jul-2021
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
A spine board was not available in the pool area..
KEEP THE SPINE BOARD VISIBLY IN THE POOL AREA. Correct By: 02-Jul-2021
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. A rope was not attached to the ring.
Provide a proper floatation device at all times. ATTACH A 30-60 FT ROPE (1/4 DIAMETER) TO THE RING BUOY. Correct By: 02-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 30-June-2021


Comments
The Certificate of Compliance is not available for the main drain cover. Keep a copy at the facility for future review.

Our records show that the main drain suction outlet covers (Lawson MLD-FGD-1212) were installed on 5-5-19. The cover have a 10 year life span and must be replaced before 5-5-29