[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The equalizer suction outlet under the skimmer is not covered with a compliant cover.
EITHER PLUG THE EQUALIZER OUTLET AT THE POOL WALL OR INSTALL A VGB COMPLIANCE COVER. Correct By: 01-Apr-2018
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection At the beginning of the inspection the free chlorine level was .2 ppm.
MAINTAIN THE CHLORINE LEVEL AT 1.0 PPM OR MORE. Correct By: 18-Aug-2017

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Combine and total chlorine, alkalinity, cyanuric acid are not being tested and recorded at the required frequency.
All facility records must be maintained and available for review upon request. TEST AND RECORD TOTAL, FREE, AND COMBINE CHLORINE AND pH EVERY 4 HOURS. ALKALINITY AND CYANURIC ACID WEEKLY, TEMPERATURE DAILY, VAC ALERT MONTHLY. Correct By: 19-Aug-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow rate of the pool exceeds the max allowable flow of the filters
All equipment must be maintained in accordance with the manufacturers specifications. TO PREVENT DAMAGING THE FILTER OR INADEQUATE FILTERING, REDUCE THE FLOW TO 63 GPM OR LESS BUT AT LEAST 37 GPM. Correct By: 19-Aug-2017
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The main fill line is directly connected to the circulation system.
Remove all cross connection hazards from the pool area. INSTALL A BACKFLOW PREVENTER ASSE 1013 ON THE FILL LINE, OR PROVIDE AN AIR GAP ON THE FILL LINE. PRIOR INSPECTION INDICATED THAT THE FILL WATER WAS SUPPLIED THROUGH A HOSE FROM A HOSE BIB WITH A ASSE 1011 BACKFLOW PREVENTER. Correct By: 01-Apr-2018
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit does not include a reagent for cyanuric acid.
OBTAIN CYANURIC ACID REAGENT AND A THERMOMETER. Correct By: 01-Apr-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 18-August-2017


Comments
THE FLOW METER WAS MOVED TO A DIFFERENT LOCATION WHICH IS 18.5 INCHES DOWNSTREAM FROM THE ELBOW ON A 2 INCH PIPE AND 18 INCHES UPSTREAM FROM THE ELBOW. IT HAS BEEN DECIDED THAT ALTHOUGH THIS IS NOT IN COMPLIANCE IT WILL NOT BE REQUIRED TO BE MOVED AT THIS TIME.

REPAIRS MUST BE MADE TO THE CHLORINATOR SO THAT IT WILL CONSISTENTLY PRODUCE THE REQUIRED LEVEL OF CHLORINE.

PER THE CONVERSATION WILL THE MANUFACTURER OF THE VAC ALERT SVRS, THE INSTALLATION ON A COMMON LINE WILL BE ACCEPTABLE IF WHEN THE TEST FOR FUNCTIONING IS PERFORMED THE SKIMMER LINES ARE TURNED OFF.

WATER LEVEL IS LOW