[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(d) / Circulation/Disinfection system is operating properly
Critical Chemical feed is not operating. Hand feed is not allowed
Repair auto chemical feed equipment before reopening the pool. Correct By: 18-Nov-2014

3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Self closing gate is not closing properly and the gate is not latching.
Repair the gate so that it closes properly and latches.. Correct By: 18-Nov-2014
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 14-November-2014


Comments
Recommend that the pool be closed. Chlorine pump is not operating. Pool can not be operated by hand feeding. Chlorine level is too high. This is an ongoing problem that has not been corrected.