3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The equalizer outlets from the skimmers are not covered with an approved cover.
COVER THE EQUALIZER OUTLETS WITH A VGB APPROVED COVER OR PLUG THE OUTLET AT THE POOL WALL
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. One skimmer box is still missing a weir.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIR IN THE SKIMMER BOX.
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
CUT THE PIPE OFF AT LEAST 2 INCHES ABOVE THE LEVEL OF THE FLOOR (ON THE PIPE FROM THE FILTER BACKWASH) TO PROVIDE AN AIR GAP.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-July-2019
Comments |
---|
Correction made since the 6-10-19 inspection -the hand rail is tight -the test kit is stored in a room less than 85 degrees -a sign is posted stating swimming alone is not recommended -the first aid kit is new -the flow meter appear to be working properly |