[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Correct By: 04-Jul-2019
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. Correct By: 13-Jun-2019
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times. Correct By: 13-Jun-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-June-2019


Comments
Our records show: The main drain suction outlet cover (AquaStar 8MF and AuuaStar WAV12) was installed 7-27-2018. The cover has a 5 year life span and must be replaced before 7-27-2023.

-When the pool is closed for the night post a sign on the fence stating "DANGER: POOL CLOSED"

MONITOR THE CYA LEVEL. CYA MUST BE 70 PPM OR LOWER. THE ONLY WAY TO LOWER CYA IS TO DRAIN PART OF THE POOL WATER AND REFILL WITH FRESH WATER.

When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA reading = 70 ppm. Alkalinity is 70 ppm - (70/3) = 57 ppm