3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is below the required level of 1 ppm.
This is a critical operational item and poses an imminent health hazard.
THE DO NOT OPEN THE POOL UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
THE END OF THE PIPE FROM THE FILTERS MUST BE ABOVE THE LEVEL OF THE FLOOR BY 2-8 INCHES
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate to the pool area was locked open.
KEEP THE GATE DOOR CLOSED.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The bottom of the fence is more than 4 inches from the ground.
ELIMINATE THE GAP BETWEEN THE GROUND AND THE BOTTOM OF THE FENCE SO THE GAP IS LESS THAN 4 INCHES. THE GAP UNDER THE GATES SHOULD BE ELIMINATED TOO. MULCH, DIRT, OR STONE CAN BE PLACED UNDER THE FENCE TO REDUCE THE GAP. BUSHES ALONE PLANTED IN FROM OF THE FENCE WOULD NOT BE ACCEPTABLE.
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Repeat Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
POST A SIGN THAT CAN BE READ FROM THE POOL AREA STATING THE LOCATION OF THE EMERGENCY PHONE.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-August-2019
Comments |
---|
ENSURE THAT THE STARTING BLOCKS WILL BE PROPERLY INSTALLED WITH ALL SCREWS NEXT YEAR. |