[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. pH adjusted to 7.5 before leaving. (OK).
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-December-2015


Comments
Humidity very high / condensation in pool room area and pump room. Rust observed on metal plate covers. HVAC system not operating properly.